Reference:
Security policy (edit with Customer reassurance module)
Delivery policy (edit with Customer reassurance module)
Return policy (edit with Customer reassurance module)
| Product version: | 4.0 |
| Approvals: | CE, cULus Listed, TÜV, CCC |
| Category in accordance with: | EN 954-1 |
| Application options: | Safety gate monitor, Instantaneous E-STOP monitoring, Light beam device mon. Type 4, Light beam device mon. Type 2 w/o t/p, Light beam device mon. Type 2 with t/p |
| Operating modes: | Single-channel, Automatic reset, Dual-channel, Manual reset, Detection of shorts across contacts, Monitored manual reset, without detection of shorts across contacts |
| Product standard: | EN 60947-5-1 |
| Standards: | EN 60204-1, EN 954-1, VDE 0113-1 |
| Supply voltage: | 24 V |
| Supply voltage type: | DC |
| Terminal style: | fixed |
| Terminal type: | Screw terminal |
| Cat. inst. saf. contacts: | 4 |
| Number of instantaneous safety contacts: | 3 |
| Number of auxiliary contacts: | 1 |
| Stop category: | 0 |
| Max. current at DC13 I (6 cycles/min): | 7.0 A |
| Max. current at AC15: | 5.0 A |
| Width dimension: | 45.0 mm |
| Height dimension: | 87.0 mm |
| Depth dimension: | 121.0 mm |
| Gross weight: | 300 g |
| Net weight: | 270 g |
| Ambient temperature: | -10 - 55 °C |