 Combined Lightning current and surge arrester (Type 1 + Type 2)

 Coordinated SPD : 4-Pole 100KA

 Cell site Surge Protector (CSP) : Lightning Surge Arrestors

 Combined Arresters Class B, SPD Type 1, SPD Class 1

 Suitable for Radio Base Stations/Mobile Radio Systemsagainst

 With end of the life Signalling Changeover Contact

Quantity
There are not enough products in stock

  • Security policy (edit with Customer reassurance module) Security policy (edit with Customer reassurance module)
  • Delivery policy (edit with Customer reassurance module) Delivery policy (edit with Customer reassurance module)
  • Return policy (edit with Customer reassurance module) Return policy (edit with Customer reassurance module)

Type DVA CSP 3P 100 FM

Part No. 900 360

SPD according to EN 61643-11 / ... IEC 61643-11 type 1 + type 2 / class I + class II

Energy coordination with terminal equipment (≤ 10 m) type 1 + type 2 + type 3

Nominal voltage (a.c.) (UN) 230 / 240 V (50 / 60 Hz)

Max. continuous operating voltage (a.c.)[L-N]/[N-PE] (UC) 264 V (50 / 60 Hz)

Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE)) 255 V (50 / 60 Hz)

Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal) 100 kA

Specific energy [L1+L2+L3+N-PE] (W/R) 2.50 MJ/ohms

Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp) 25 / 100 kA

Specific energy [L-N]/[N-PE] (W/R) 156.25 kJ/ohms / 2.50 MJ/ohms

Nominal discharge current (8/20 µs) (In) 25 / 100 kA

Voltage protection level [L-N]/[N-PE] (UP) ≤ 1.5 kV / ≤ 1.5 kV

Follow current extinguishing capability [L-N]/[N-PE] (Ifi) 25 kArms / 100 Arms

Follow current limitation/Selectivity no tripping of a 20 A gG fuse up to 25 kArms (prosp.)

Response time (tA) ≤ 100 ns

Max. backup fuse (L) up to IK = 25 kArms 315 A gG

Max. backup fuse (L) up to IK > 25 kArms 200 A gG

Max. backup fuse (L-L') 125 A gG

Temporary overvoltage (TOV) [L-N] (UT) – Characteristic 440 V / 120 min. – withstand

Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic 1200 V / 200 ms – withstand

Additional abnormal voltage test: 485 V AC / 50 Hz for 24 h withstand

Operating temperature range [parallel]/[series] (TU) -40°C...+80°C / -40°C...+60°C

Operating state/fault indication green / red

Number of ports 1

Cross-sectional area (L1, L1', L2, L2', L3, L3', N, N', PE, 9 ) (min.) 10 mm2

 solid / flexible

Cross-sectional area (L1, L2, L3, N, PE) (max.) 50 mm2

 stranded / 35 mm2

 flexible

Cross-sectional area (L1', L2', L3', N', 9 ) (max.) 35 mm2

 stranded / 25 mm2

 flexible

For mounting on 35 mm DIN rails acc. to EN 60715

Enclosure material thermoplastic, red, UL 94 V-0

Place of installation indoor installation

Degree of protection IP 20

Capacity 8 module(s), DIN 43880

Approvals KEMA

Type of remote signalling contact changeover contact

Switching capacity (a.c.) 250 V / 0.5 A

Switching capacity (d.c.) 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A

Cross-sectional area for remote signalling terminals max. 1.5 mm2

 solid / flexible

Weight 1,3 kg

Customs tariff number (Comb. Nomenclature EU) 85363090

GTIN 4013364111332

PU 1 pc(

16 other products in the same category: