Type: EOCR- i3MZ-WRDUW
(Display built-in)
With – Over current, Undercurrent, Earth Fault, Ammeter and
Communications (RS485 Modbus)
Specification
Supply Voltage : 100 ~ 240VAC/DC
Load Current Setting Range : 0.5 ~ 80A
Delay Time (D-Time) : 0 ~ 200 sec
Operating Time (O-Time) : 0.2 ~ 30 sec
Inverse & Thermal : 1 ~ 30 classes
Undercurrent : OFF, 1 ~ 10 sec
Ground Fault : GF delay time (EDT): 0~30s, GF O-time (ET): 0.05~10s
Earth Fault : Setting Range: Off, 0.05~10A
Contact Ratings : Overload: 1a1b, GR: 1a, (3A / 250VAC)
Phase Loss : OFF, 0.5 ~ 5S Adjustable
Phase Reverse : within 0.15s
For higher motor setting currents Please use separate CT upto 800 / 5A